TOPDRIVE VFD (EMC) ROZ1-K (AS) 0,6/1 kV

TOPDRIVE VFD (EMC) ROZ1-K (AS) 0,6/1kV cable has been specially designed for Variable Frequency Drive Motors and installations where it is necessary to limit the effects of electromagnetic interference (EMI). This is a flexible cable for fixed installations, for variable speed motors or pumps.

TOPDRIVE VFD (EMC) ROZ1-K (AS) cable performance

Electrical performance

LOW VOLTAGE  0,6/1 kV

Standard

IEC 60502-1 / IEC 60092-353

Approvals

BUREAU VERITAS / DNV-GL / ABS / LLOYD’S REGISTER / RoHS / CE / UKCA

CPR Construction Product Regulation

Cca – s1a, d1, a1

Thermal performance

Maximum conductor temperature: 90ºC.

Maximum short-circuit temperature: 250ºC (max. 5 s).

Minimum service temperature: -40ºC (fixed and protected installations).

Fire performance

Flame non-propagation based on EN 60332-1 and IEC 60332-1.

Fire non-propagation based on EN 60332-3/IEC 60332-3 and EN 50399.

Reaction to fire CPR: Cca – s1a, d1, a1 , according to EN 50575.

LSHF (Low Smoke Halogen Free) according to EN 60754-1 and IEC 60754-1.

Low smoke emission based on EN 61034 and IEC 61034.

Light transmittance > 80%

Low corrosive gases emission based on EN 60754-2 and IEC 60754-2.

Mechanical performance

Minimum bending radius: x10 cable diameter.

Impact resistance: AG2 Medium severity.

Environmental performance

Chemical & Oil resistance: Acceptable.

UV resistant based on EN 50618.

Water resistance: AD5 Jets.

Other

Meter by meter marking.

Ripcord.

Electric fields resistant.

Installation conditions

Open Air.

Buried.

In conduit.

Applications

Industrial use.

Variable Frequency Drive (VFD).

Electromagnetic protection.

TOPDRIVE® VFD (EMC) ROZ1-K (AS) cable design

Conductor

Electrolytic annealed copper conductor, class 5 (flexible), according to EN 60228 and IEC 60228.

Protective Conductor

The ground conductor is divided into three conductors; the equivalent cross-section is approximately 50% of the section of the phase conductor. For 4G cables, ground conductor has the same cross-section as the phase conductors.

Insulation

Cross-linked polyethylene type HF XLPE 90ºC according to IEC 60092-360. The standard identification of insulated conductors is the following:

3 x + 3 G Grey + Brown + Black +Green/yellow (3 G) (from 6mm2 onwards)

4 G  Grey + Brown + Black + Green/yellow (up to 4 mm2) 

Assembly of cores

For 3 x + 3 G cables, the three phase conductors are cabled helically with the three protective conductors distributed in the interstices. For 4 G cables, the three phase conductors and protection conductor are cabled helically.

Screen

Aluminium-polyester tape screen, helically placed over the insulated conductors. Over the tape there is a tinned copper braid screen. The tape and the braid act as a double screen to cut out all of the electromagnetic interference, with a minimum total section of 10% of the phase conductor, ensuring a total shielding coverage.

Outer sheath

Polyolefin LSHF outer sheath type SHF1 according to IEC 60092-360. black color. The ripcord allows you to tear the outer sheath without damaging the screen.

Category:

Flexible EMC LSZH screened cable for Variable Frequency Drive motors (VFD cables) and installation on ships and vessels.